5.5 Commissioning the New Main Way

Context
Procedure
Step 1 Set parameters for general input units on the ECC800-Pro WebUI.
1.
Table 5-3 Power distribution settings for a general input unit
Path
Monitoring > Power
Distribution > General
Input Unit > Running
Parameters > Power
Distribution Settings
Issue 06 (2020-04-22)
In the new main way scenario, general input units and power distribution units
communicate with the ECC800-Pro using the Modbus-MAC protocol. After the general
input units and power distribution units properly connect to the ECC800-Pro, the
ECC800-Pro automatically identifies the units.
Then, you need to set parameters for the general input units and power distribution units;
otherwise, a false alarm may be generated.
Set parameters for general input unit 1.
Copyright © Huawei Technologies Co., Ltd.
Parameter
Default
Name
Value
Rated system
50
frequency
Rated system
380
voltage
Rated system
250
current
NOTE
This parameter is
not displayed for
some general
input units.
System CT ratio
250
NOTE
This parameter is
not displayed for
some general
input units.
Upper load
80
current threshold
Lower load
60
current threshold
5 Power-On Commissioning
Setting
Set based on actual
conditions.
Set based on actual
conditions.
Set based on actual
conditions.
NOTE
Set this parameter to a value
consistent with the information
on the nameplate of the general
input unit. For example, if the
model is NMW-0250 AC, set
Rated system current to 250
A.
Set based on actual
conditions.
For example, if Rated
system current is 250 A, set
System CT ratio to 250.
When the load current
exceeds the preset value, an
alarm is generated.
When the load current
exceeds the preset value, an
alarm is generated.
103