Huawei ECC800 User Manual page 87

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
BCB Port
Figure 3-51 BCB port pins
Table 3-77 BCB_1–BCB_4 port pin definitions
Pin
1
2
3
4
Table 3-78 BCB_IN and BCB_OUT cascading port pin definitions
Pin
1
Issue 06 (2020-04-22)
Defi
Signal
nitio
Description
n
OL
Monitors
whether the
BCB
connects to
the signal
input port.
STA
Monitors the
battery circuit
breaker
DRV
Controls
battery circuit
breaker trip
and outputs
12 V driving
signals
GND
Secondary
side ground
Defi
BCB_IN
nitio
Signal
n
Descriptio
n
OL
Specifies
whether the
BCB
connects to
Copyright © Huawei Technologies Co., Ltd.
Status Description
Grounded: BCB
connected.
Disconnected: BCB
not connected.
Grounded: The battery
circuit breaker is ON.
Disconnected: The
battery circuit breaker
is OFF.
0 V: There is no
driving signal for BCB
tripping.
12 V: There is a
driving signal for BCB
tripping.
BCB_OUT
Status
Signal
Description
Description
Specifies
Grounded:
whether the
BCB
cascaded
connected.
BCBs
Disconnecte
3 Device Description
Initial
Descriptio
Status
n
Disconnecte
The four
d
BCBs can
separately
manage
tripping of
four battery
routes.
Disconnecte
d
0V
Initial
Descripti
Status
on
Disconnec
Receives
ted
BCB
commands
sent by the
76

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecc800-pro

Table of Contents