Huawei ECC800 User Manual page 279

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Table 8-37 Adding a T/H sensor
Path
Choose System
Settings >
Device
Management
and click Add
Device. The
parameters for
adding devices
are displayed.
3.
Step 3 Check functions of the T/H sensor.
Table 8-38 Function check
Check Method
Check the running information
about the T/H sensor on the
WebUI.
Set T/H sensor alarm thresholds.
Issue 06 (2020-04-22)
Parameter
Name
Device attribute
Device type
Connect to
Communications
Port
Device address
Click Test Connect to check whether the T/H sensor connects to the ECC800-Pro
properly.
If the T/H sensor connects to the ECC800-Pro properly, click Confirm. The
connected devices are displayed in the Number of connected devices list.
If the T/H sensor does not connect to the ECC800-Pro properly, check whether the
cable between the T/H sensor and the ECC800-Pro is connected properly, whether
the T/H sensor and ECC800-Pro are running properly, and whether the input
parameters are consistent with the T/H sensor parameters.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select Sensor from the drop-down list box.
Select T/H sensor from the drop-down list box.
Select ECC800 from the drop-down list box.
Select COM3 from the drop-down list box.
NOTE
The setting example indicates that the T/H sensor is
connected to the COM3 port on the ECC800-Pro. If the
T/H sensor is connected to another port, enter the number
of the connected port.
In this example, Device address is set to 1. During
actual configuration, set the device address for the
T/H sensor based on the actual situation.
Normal Connection Status
Choose Monitoring > Aisle > T/H Sensor Group >
T/H Sensorn > Running Info, and check the current
T/H and NTC information of the cabinet.
Choose Monitoring > Aisle > T/H Sensor Group >
T/H Sensorn > Running Parameters, and set High
temperature alarm threshold, Low temperature
alarm threshold, High humidity alarm threshold,
Low humidity alarm threshold, NTC1-6 high
temperature alarm threshold and NTC1-6 low
temperature alarm threshold as required.
NOTE
The default values of High temperature alarm threshold,
Low temperature alarm threshold, High humidity alarm
threshold, Low humidity alarm threshold, NTC1-6 high
temperature alarm threshold and NTC1-6 low
temperature alarm threshold are 30.0° C, 5.0° C, 85.0%
RH, 15.0% RH, 45° C and 10° C respectively.
8 FAQ
268