Huawei ECC800 User Manual page 252

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Step 2 Add a PMAC625.
1.
2.
Table 8-12 Adding a PMAC625
Path
Choose System
Settings >
Device
Management
and click Add
Device. The
parameters for
adding devices
are displayed.
3.
4.
----End
Issue 06 (2020-04-22)
Figure 8-18 Communications address of the PMAC625
Log in to the ECC800-Pro WebUI as an administrator.
Add a PMAC625.
Parameter
Name
Device attribute
Device Type
Connect To
Communications
Port
Device Address
Click Test Connect to check whether the PMAC625 connects to the ECC800-Pro
properly.
If the PMAC625 connects to the ECC800-Pro properly, click Confirm. The
connected devices are displayed in the Number of connected devices list.
If the PMAC625 does not connect to the ECC800-Pro properly, check whether the
cable between the PMAC625 and the ECC800-Pro is connected properly, whether
the PMAC625 and ECC800-Pro are running properly, and whether the input
parameters are consistent with the PMAC625 parameters.
Choose Monitoring > System > ETH Converter Group > ETH Converter n >
Running Parameters and set Device name to ETH Converter n_Device name.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select Electricity Meter from the drop-down list
box.
Select PMAC625 from the drop-down list box.
Select ETH Converter n from the drop-down list
box.
Select COM1/COM2 from the drop-down list box.
In this example, Device Address is set to 100.
During actual configuration, set the device address
for the PMAC625 based on the actual situation.
8 FAQ