Specifications
Table 3-41 Skylight actuator technical specifications
Item
Power input
POE port
Wireless
communication
AI/DI port
DO output
DI input
BLINK button
Address DIP
switch
E-label
Indicators
Table 3-42 Skylight actuator indicators
Indicat
or
Power
RUN
Issue 06 (2020-04-22)
Specifications
DC input: Terminal, with input voltage of 36 V DC–60 V DC
POE input: One POE port that complies with IEEE802.3 at
FE communication with the rate of 10/100M
One wireless port that complies with IEEE802.15.4, mutual backup with
FE communication
Two AI/DI ports for detecting fire extinguishing linkage signals; smoke
detection signals also supported
One 12 V DC power output for controlling the skylight magnetic lock;
driving six skylight magnetic locks simultaneously
One DI input port for connecting to the window open button
Press the button for less than 1 second to start blinking.
Hold down the button for 1–5 seconds to search for a network and
start networking.
Hold down the button for more than 10 seconds to clear network
parameters.
4-pin address DIP switch
Supported
Color
Name
Green
Power input
status
indicator
Green
Operating
status
indicator
Copyright © Huawei Technologies Co., Ltd.
Status
Description
Steady on
The power input is normal.
Off
There is no power input.
Off
The power is abnormal or the
board program is loading.
Blinking at
The skylight actuator
long intervals
successfully registers with the
ECC800-Pro and the software
runs properly (the indicator
blinks at 0.5 Hz, on for 1s and
then off for 1s).
Blinking at
The communication fails or the
3 Device Description