8.1.6.32 How to Set and Add the T/H Sensor (BOM Number: 02310NBS)?

If a T/H sensor is installed, perform the following steps to configure it.
Prerequisites
One end of the straight-through cable has been connected to the RS485_IN port on the T/H
sensor, and the other end has been connected to the COM port on the ECC800-Pro or the
UIM20A expansion module.
Context
This section describes how to set and add a T/H sensor by using the COM port on the
ECC800-Pro as an example.
Procedure
Step 1 Set the T/H sensor device address.
Set the T/H sensor device address through the DIP switch on the T/H sensor.
Toggle switches 1 to 6 of the DIP switch specify the device address in binary mode. ON
indicates 1, and OFF indicates 0.
Table 8-34 Setting a device address
Address
1
2
3
4
Step 2 Add a T/H sensor.
1.
2.
Table 8-35 Adding a T/H sensor
Path
Choose System
Settings >
Device
Issue 06 (2020-04-22)
Toggle
Switch 1
ON
OFF
ON
OFF
Log in to the ECC800-Pro WebUI as an administrator.
Add a T/H sensor.
Parameter
Name
Device attribute
Device type
Copyright © Huawei Technologies Co., Ltd.
Toggle
Toggle
Switch 2
Switch 3
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
Setting
Select Sensor from the drop-down list box.
Select T/H sensor from the drop-down list box.
Toggle
Toggle
Switch 4
Switch 5
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF