8.1.6.33 How Should I Set and Add the T/H Sensor (BOM Number:
02311FQG/02312PBL)?
Prerequisites
One end of the straight-through cable has been connected to the RS485_IN port on the T/H
sensor, and the other end has been connected to the COM port on the ECC800-Pro or the
UIM20A expansion module.
Context
This section describes how to set and add a T/H sensor by using the COM port on the
ECC800-Pro as an example.
Procedure
Step 1 Set the T/H sensor device address.
Set the T/H sensor device address through the DIP switch on the T/H sensor.
Toggle switches 1–6 are used to set device addresses, toggle switch 7 is reserved, and toggle
switch 8 is used to switch the temperature unit.
Device addresses are set in binary coding format in the range of 1–63. The first bit is the least
significant bit, and the sixth bit is the most significant bit. ON indicates 1, and OFF indicates
0.
Figure 8-22 T/H sensor DIP switch
Step 2 Add a T/H sensor.
1.
2.
Issue 06 (2020-04-22)
Log in to the ECC800-Pro WebUI as an administrator.
Add a T/H sensor.
Copyright © Huawei Technologies Co., Ltd.
8 FAQ
267