ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Figure 3-29 WLDS600 water sensor
(1) Tie line
(4) Extension line
Table 3-54 WLDS600 water sensor specifications
Item
Dimensions (L
x W x H)
Power supply
Issue 06 (2020-04-22)
(2) Water leakage location cable
(5) Water leakage locator
Two types (A and B) of end caps are delivered. The site may support only one type.
Connect either end cap to the cable. After the cable is connected and the water leakage locator is
powered on and initialized, if the buzzer keeps buzzing and the alarm location is a stable value that
is greater than the total length of the water leakage location cable, replace the end cap with the other
end cap.
Specification
70 mm x 58 mm x 86 mm± 1
9–16 V DC or 9–16 V AC
Copyright © Huawei Technologies Co., Ltd.
3 Device Description
(3) End cap A (B)
56