ECC800 Data Center Controller
User Manual (for ECC800-Pro)
4.
Step 11 Ensure that Link smoke alarm with skylight open on the Linkage Group tab page is on.
Step 12 Check the Link smoke alarm with skylight open linkage function.
Table 6-32 Function check
Check Method
When the skylight in the aisle is closed,
press the skylight button to open the
skylight.
Simulate a smoky environment under the
smoke sensor or the multi-func sensor.
----End
Follow-up Procedure
After Link smoke alarm with skylight open linkage is triggered and the alarm is cleared,
perform the following operations:

6.6.2 FusionModule800 Linkage Control

Prerequisites
Issue 06 (2020-04-22)
Figure 6-39 Link smoke alarm with skylight open logic
Click Submit.
Click Link smoke alarm with skylight open on the Linkage Group tab page. If it is in on state, the
corresponding logic configurations on the Linkage Logic List tab page are available. If it is in off state,
the corresponding logic configurations on the Linkage Logic List tab page are unavailable.
Press the reset button on the smoke sensor to clear the alarm.
Close the skylight manually.
You have obtained the IP address of the ECC800-Pro as well as the user name and
password used for WebUI login.
A PC with an IP address in the same network segment as that of the ECC800-Pro is
prepared, and the PC has connected to port WAN1 on the ECC800-Pro.
Copyright © Huawei Technologies Co., Ltd.
Expected Result
Smoke DI alarm is displayed on the
active alarm page of the app or WebUI.
The skylight is opened.
6 Feature Description