6.4.1.4 Commissioning the Door Status Sensor (Connected to the
ECC800-Pro)
Context
If the sensor is preinstalled, only check its settings.
Procedure
Step 1 For a single cabinet, set the door status sensor parameters.
1.
2.
3.
4.
5.
6.
Step 2 If the number of cabinets is less than or equal to 2, set the door status sensor parameters.
1.
2.
3.
4.
5.
6.
7.
8.
Step 3 If there are more than two cabinets, set the door status sensor parameters.
1.
Issue 06 (2020-04-22)
Log in to the ECC800-Pro WebUI as an administrator.
Choose System Settings > Signal Name Modify. The Batch Signal Configuration
page is displayed.
Set Device type to ECC800 and Device name to ECC800, and click OK.
On the query result tab page, set the new signal name of AI/DI_3 to Door1 and click
Submit.
Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_3 Port
Settings.
Set Door1 sensor to Enable, set Door1 sensor type to Door sensor, and click Submit.
Log in to the ECC800-Pro WebUI as an administrator.
Choose System Settings > Signal Name Modify. The Batch Signal Configuration
page is displayed.
Set Device type to ECC800 and Device name to ECC800, and click OK.
On the query result tab page, set the new signal name of AI/DI_3 to Door1 and click
Submit. Change the new signal name of AI/DI_5 to Door2 and click Submit.
Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_3 Port
Settings.
Set Door1 sensor to Enable, set Door1 sensor type to Door sensor, and click Submit.
Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_5 Port
Settings.
Set Door2 sensor to Enable, set Door2 sensor type to Door sensor, and click Submit.
Set door status sensor parameters for the IT cabinet by referring to step 1.
Copyright © Huawei Technologies Co., Ltd.
Normal Connection Status
Door1 DI alarm is generated on the active alarm page
of the app or WebUI.