6.1 Access Management

6.1.1 Commissioning a Door Status Sensor

6.1.1.1 Commissioning a Door Status Sensor (Connected to the AI/DI port
on the independent deployment AI_DI unit)
If a door status sensor is installed, perform the following steps to configure it.
Context
Procedure
Step 1 Set parameters for a door status sensor.
1.
2.
3.
4.
5.
Issue 05 (2019-09-16)
To use the AI/DI sensor, enable the corresponding AI/DI port and name the sensor. After
that, the specific alarm can be reported.
If the sensor is prefabricated, only check its settings.
If multiple door status sensors are connected, commission one door status sensor first
and then commission the other door status sensors in the same way.
In this example, the door status sensor is connected to the AI/DI_1 port on the independent deployment
AI_DI 1.
Log in to the ECC800 WebUI as an administrator.
Choose System Settings > Signal Name Modify. The Batch Signal Configuration
page is displayed.
Set Device Type to Independent Deployment AI_DI Unit, set Device Name to
Independent Deployment AI_DI1 Unit, and click OK.
On the query result tab page, set the new signal name of AI/DI_1 to Door1 and click
Submit.
Order number of door sensor name is same as cabinet.
Choose Monitoring > System > Independent Deployment AI_DI Unit Group >
Independent Deployment AI_DI1 Unit > Running Parameters > AI/DI_1 Port
Settings.