ECC800 Data Center Controller
User Manual
BCB Port
Figure 3-42 BCB port pins
Table 3-61 BCB_1–BCB_4 port pin definitions
Pin
1
2
3
4
Issue 05 (2019-09-16)
When an iBOX manages multiple battery strings, first connect the Hall effect sensors on the positive
and negative cables of battery string 1 respectively to the corresponding ports on the iBOX. Then
connect the Hall effect sensors on battery string 2 to the iBOX in the same way, and so on.
If the positive or negative battery string cable is too thick to be routed through the Hall effect sensor,
or the measurement range of the Hall effect sensor is not enough, use multiple Hall effect sensors to
monitor the current of one battery string. The iBOX supports the sum of the monitoring results of
multiple Hall effect sensors, which is set through Multi-Hall cur. setting.
The value of Multi-Hall cur. setting equals the number of positive or negative Hall effect sensors in
a single battery string and should be greater than or equal to 1.
Defini
Signal
tion
Description
OL
Monitors
whether the
BCB box is
connected
STA
Monitors the
battery circuit
breaker
DRV
Controls
battery circuit
breaker trip
and outputs 12
V driving
signals
GND
Secondary side
Copyright © Huawei Technologies Co., Ltd.
Status
Initial
Description
Status
Grounded:
Disconnec
BCB
ted
connected.
Disconnecte
d: BCB not
connected.
Grounded:
Disconnec
The battery
ted
circuit
breaker is
ON.
Disconnecte
d: The
battery
circuit
breaker is
OFF.
0 V: There
0 V
is no driving
signal for
BCB
tripping.
12 V: There
is a driving
3 Device Description
Remarks
The four BCBs can
separately manage
tripping of four battery
routes.