6.1.3 Commissioning the Exit Button, Skylight Button,
Atmosphere Light, Emergency Button, and Magnetic Lock
Procedure
Step 1 Check functions of the exit button.
Table 6-7 Function commissioning
Check Method
Attempt to open the door by pressing the
exit button when the aisle door is closed.
Step 2 Check functions of the skylight button.
Table 6-8 Function commissioning
Check Method
Attempt to open the door by pressing the
skylight button when the aisle door is
closed.
Step 3 Check functions of the atmosphere light.
Table 6-9 Function commissioning
Check Method
Press the atmosphere light button.
Step 4 Check functions of the emergency button.
Table 6-10 Function commissioning
Check Method
Attempt to open the door by
pressing the emergency button
when the aisle door is closed.
Issue 05 (2019-09-16)
Normal Connection
Status
The aisle door is
opened successfully.
Copyright © Huawei Technologies Co., Ltd.
Normal Connection Status
The aisle door is opened successfully.
Normal Connection Status
The skylight can be opened manually.
Normal Connection Status
The atmosphere light is steady blue.
Follow-up Procedure
You need to restore the
emergency button.