ECC800 Data Center Controller
User Manual
Context
IT cabinets, network cabinets, and smart cooling products support power management. The
ECC800 connected to an IT cabinet is used as an example in this section.
Procedure
Step 1 Log in to the ECC800 WebUI as an administrator.
Step 2 Choose Home > Plan View > Modify Device and click Apply Power Distribution
Standard Configuration to use the default configuration to configure electricity for devices
in the smart module. The following scenarios support the function of applying default
electricity configuration:
Step 3 Double-click a network cabinet to access the Basic Configuration page.
Step 4 Check whether the branch information in Apply Power Distribution Standard
Configuration is consistent with the actual situation, and set electricity configuration
parameters such as Device Name, Cabinet height, Power system, Number of power
supplies, and Rated cabinet power as required.
Table 6-25 Basic configuration
Parameter
Device Name
Cabinet height
Cabinet width
Power
Distrib
ution
Param
eter
Setting
s
Issue 05 (2019-09-16)
N+1 scenario: The system has only one power distribution cabinet and is working in
single-power supply mode.
2N non-isolation scenario: The system has only one power distribution cabinet and is
working in dual-power supply mode.
2N isolation scenario: The system has two power distribution cabinets and is working in
single-power supply mode.
For details about the power distribution solution, refer to the power distribution wiring diagram supplied
with the product.
The settings in the following table are used as examples to describe the basic configuration.
Setting
IT Cabinet 101
42
600
Power
Single-phase
system
Numb
2
er of
power
supplie
s
Rated
6.00
cabinet
power
Copyright © Huawei Technologies Co., Ltd.
6 Feature Description
Description
Set based on the actual device
name.
U space quantity of the cabinet.
The width of the cabinet.
Set single-phase or three-phase
based on the actual power supply.
rPDU quantity.
Set based on the actual rated
power of the cabinet.
142