8.1.8.31 How to Set and Add the WLDS600 Water Sensor?

If a water sensor is installed, perform the following steps to configure it.
Prerequisites
One end of the straight-through cable has been connected to the RJ45 port on the WLDS600
water sensor, and the other end has been connected to the energized COM port on the
ECC800.
Procedure
Step 1 The default communications address 1 of the water sensor is used for connecting to the
ECC800.
Step 2 Log in to the ECC800 WebUI as an administrator.
Step 3 Add the water sensor.
Table 8-26 Adding the water sensor
Path
Choose System
Settings >
Device
Management
and click Add
Device. The
parameters for
adding devices
are displayed.
Step 4 Click Test Connect to check whether the water sensor connects to the ECC800 properly.
Issue 05 (2019-09-16)
Normal Connection Status
Leak DI alarm is generated on
the active alarm screen of the
app or on the WebUI.
Parameter
Name
Device attribute
Device Type
Connect To
Communications
Port
Device Address
Copyright © Huawei Technologies Co., Ltd.
Alarm Clearance Method
Wipe dry the water detection
cable. The alarm disappears
automatically.
Setting
Select Sensor from the drop-down list box.
Select Water Sensor from the drop-down list box.
Select ECC800 from the drop-down list box.
Select COM1 from the drop-down list box.
NOTE
The setting example indicates that the water sensor is
connected to the COM1 port on the ECC800. If the water
sensor is connected to another port, enter the number of
the connected port.
In this example, Device Address is set to 1. During
actual configuration, set the device address for the
water sensor based on the actual situation.