ECC800 Data Center Controller
User Manual
Parameter
rPDU-A01
rPDU-B01
Branch auto-fill
mode
Issue 05 (2019-09-16)
Setting
PDU80001 > 1QF1(L1)
PDU80001 > 2QF1(L1)
Ascending order
Descending order
Copyright © Huawei Technologies Co., Ltd.
6 Feature Description
Description
Select a power distribution device
and power distribution branch for
the rPDU numbered rPDU-A01 in
the cabinet.
Select a power distribution device
and power distribution branch for
the rPDU numbered rPDU-B01 in
the cabinet.
If the branch for the first
cabinet is 1QF1(L1),
2QF1(L1), the branches for
subsequent cabinets are
1QF2(L2), 2QF2(L2), and the
like.
If the branch for the first
cabinet is 1QF10(L1),
2QF10(L1), the branches for
subsequent cabinets are
1QF9(L3), 2QF9(L3), and the
like.
143