User Manual (for ECC800-Pro)
2.
3.
4.
5.
6.
7.
8.
Step 2 Check functions of water sensors.
Table 8-31 Function check
Check Method
Immerse the water
detection cable in water.
----End

8.1.7.34 How Can I Set and Add a WLDS600 Water Sensor?

If a water sensor is installed, perform the following steps to configure it.
Prerequisites
One end of the straight-through cable has been connected to the RJ45 port on the
WLDS600 water sensor, and the other end has been connected to the energized
COM port on the ECC800-Pro.
Procedure
Step 1 The default communications address 1 of the water sensor is used for connecting
to the ECC800-Pro.
Step 2 Log in to the ECC800-Pro WebUI as an administrator.
Step 3 Add the water sensor.
Issue 02 (2020-09-07)
Choose System Settings > Signal Name Modify. The Batch Signal
Configuration page is displayed.
Set Device type to ECC800, set Device name to ECC800, and click OK.
On the query result tab page, set the new signal name of AI/DI_1 to Leak
and click Submit.
Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_1
Port Settings.
Set Leak sensor to Enable and click Submit.
Confirm that Leak sensor type is automatically identified as Leak
sensor(Rope).
Click Unhide All Advanced Signals, then click Power Supply Parameters.
Ensure that III power supply enable(AIDI_1/DO) is Yes.
Copyright © Huawei Technologies Co., Ltd.
Normal Connection
Status
Leak DI alarm is
generated on the active
alarm screen of the app
or on the WebUI.
Alarm Clearance
Method
Wipe dry the water
detection cable. The
alarm disappears
automatically.