ECC800 Data Center Controller
User Manual (for ECC800-Pro)
3.
----End

8.1.7.14 How Can I Set and Add a 5G DC Power Supply (Modbus-RTU)?

Prerequisites
One end of the straight-through cable has been connected to the RS485 port on
the SMU02C in the MTS9604B-N20B1 cabinet, and the other end has been
connected to the COM port on the ECC800-Pro collector or ETH converter.
Procedure
Step 1 Connect the RS485 communications port on the SMU02C.
Figure 8-12 RS485 communications port
Step 2 Add a 5G DC power supply.
1.
2.
Issue 02 (2020-09-07)
Path
Parameter
Device
Address
Click Test Connect to check whether the PDU8000 connects to the ECC800-
Pro properly.
If the PDU8000 connects to the ECC800-Pro successfully, click Confirm.
The connected devices are displayed in the Number of connected
devices list.
If the connection fails, check whether the PDU8000 is properly connected
to the ECC800-Pro, whether the PDU8000 and ECC800-Pro are running
properly, and whether the parameter settings are consistent with the
PDU8000 parameters.
Log in to the ECC800-Pro WebUI as an administrator.
Add a 5G DC power supply.
Copyright © Huawei Technologies Co., Ltd.
Setting
In this example, Device Address is set to 1.
During actual configuration, set the device
address for the PDU8000 based on the
actual situation.