8.1.7.3 How Can I Set and Add a UPS2000G_L (Modbus-RTU)?
Prerequisites
One end of the straight-through cable has been connected to the CAN
communications port on the rear panel of the UPS2000G_L, and the other end has
been connected to the COM port on the ECC800-Pro or ETH converter.
Procedure
Step 1 Set the communications address parameters for the UPS2000G_L.
Step 2 Add a UPS2000G_L.
1.
2.
Issue 02 (2020-09-07)
Path
Parameter
for adding
Communicati
devices are
ons Port
displayed.
Device
Address
Click Test Connect to check whether the UPS2000G-A connects to the
ECC800-Pro properly.
–
If the connection succeeds, click Confirm. The connected devices are
displayed in the Number of connected devices list.
–
If the connection fails, check whether the UPS2000G is properly
connected to the ECC800-Pro, whether the UPS2000G and ECC800-Pro
are running properly, and whether the parameter settings are consistent
with the UPS2000G parameters.
NO TE
The section describes how to add a UPS2000G-A in a single UPS scenario. In a parallel UPS
scenario, if the common communications address of the Modbus card is added to the
ECC800-Pro, all UPS2000G-As can be connected to the ECC800-Pro.
NO TE
UPS2000-G-6KRTLL User Manual .
For details, see the
Log in to the ECC800-Pro WebUI as an administrator.
Add a UPS2000G_L.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select COM2 from the drop-down list box.
NOTE
The setting example indicates that the
UPS2000G-A is connected to the COM2 port on
the ECC800-Pro. If the UPS2000G-A is
connected to another port, enter the number of
the connected port.
In this example, Device Address is set to 1.
During actual configuration, set the device
address for the UPS2000G-A based on the
actual situation.
8 FAQ