ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Step 3 Check functions of the T/H sensor.
Table 8-45 Function commissioning
Check Method
Check the running
information about the T/H
sensor on the WebUI.
Set T/H sensor alarm
thresholds.
----End

8.1.8 How Can I Restore Factory Settings?

Context
Restoring factory settings will restore parameters to their default values. Back up
data before performing this operation. Perform this operation with caution.
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Choose Maintenance > Configuration File and click Restore Factory Settings.
Step 3 Enter the password currently used for logging in to the WebUI and click Submit.
----End
Issue 02 (2020-09-07)
NO TICE
Copyright © Huawei Technologies Co., Ltd.
Normal Connection Status
Choose Monitoring > Aisle > T/H Sensor Group
> T/H Sensorn > Running Info, and check the
current T/H and NTC information of the cabinet.
Choose Monitoring > Aisle > T/H Sensor Group
> T/H Sensorn > Running Parameters, and set
High temperature alarm threshold, Low
temperature alarm threshold, High humidity
alarm threshold, Low humidity alarm
threshold, NTC1-6 high temperature alarm
threshold and NTC1-6 low temperature alarm
threshold as required.
NOTE
The default values of High temperature alarm
threshold, Low temperature alarm threshold, High
humidity alarm threshold, Low humidity alarm
threshold, NTC1-6 high temperature alarm
threshold and NTC1-6 low temperature alarm
threshold are 30.0°C, 5.0°C, 85.0% RH, 15.0% RH,
45°C and 10°C respectively.
8 FAQ