Huawei ECC800-Pro User Manual page 324

Data center controller
Hide thumbs Also See for ECC800-Pro:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Address
3
4
Step 2 Add a T/H sensor.
1.
2.
3.
Step 3 Check functions of the T/H sensor.
Issue 02 (2020-09-07)
Toggle
Switch 1
ON
OFF
Log in to the ECC800-Pro WebUI as an administrator.
Add a T/H sensor.
Table 8-42 Adding a T/H sensor
Path
Parameter
Choose
Device
System
attribute
Settings >
Device Type
Device
Management
and click Add
Connect To
Device. The
parameters
Communica
for adding
tions Port
devices are
displayed.
Device
Address
Click Test Connect to check whether the T/H sensor connects to the ECC800-
Pro properly.
If the T/H sensor connects to the ECC800-Pro successfully, click Confirm.
The connected devices are displayed in the Number of connected
devices list.
If the connection fails, check whether the T/H sensor is properly
connected to the ECC800-Pro, whether the T/H sensor and ECC800-Pro
are running properly, and whether the parameter settings are consistent
with the T/H sensor parameters.
Copyright © Huawei Technologies Co., Ltd.
Toggle
Toggle
Switch 2
Switch 3
ON
OFF
OFF
ON
Setting
Select Sensor from the drop-down list box.
Select T/H sensor from the drop-down list
box.
Select ECC800 from the drop-down list box.
Select COM3 from the drop-down list box.
NOTE
The setting example indicates that the T/H sensor
is connected to the COM3 port on the ECC800-
Pro. If the T/H sensor is connected to another
port, enter the number of the connected port.
In this example, Device Address is set to 1.
During actual configuration, set the device
address for the T/H sensor based on the
actual situation.
Toggle
Toggle
Switch 4
Switch 5
OFF
OFF
OFF
OFF
8 FAQ
Toggle
Switch 6
OFF
OFF
313