Huawei ECC800-Pro User Manual page 73

Data center controller
Hide thumbs Also See for ECC800-Pro:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Figure 3-30 WLDS600 water sensor
(1) Tie line
(4) Extension line
Table 3-56 WLDS600 water sensor specifications
Item
Dimensions (L
x W x H)
Power supply
Impulse
current
Power
dissipation
Power,
communicatio
n connector
Issue 02 (2020-09-07)
(2) Water leakage location cable
(5) Water leakage locator
NO TE
● Two types (A and B) of end caps are delivered. The site may support only one type.
● Connect either end cap to the cable. After the cable is connected and the water leakage
locator is powered on and initialized, if the buzzer keeps buzzing and the alarm location
is a stable value that is greater than the total length of the water leakage location
cable, replace the end cap with the other end cap.
Specification
70 mm x 58 mm x 86 mm±1
9–16 V DC or 9–16 V AC
≤ 450 mA
< 2 W
RJ45 female connector 1 piece
Copyright © Huawei Technologies Co., Ltd.
3 Device Description
(3) End cap A (B)
62

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents