ECC800 Data Center Controller
User Manual (for ECC800-Pro)

8.1.7.8 How Can I Set and Add an SVG-In-Power (Modbus-RTU)?

Prerequisites
One end of the straight-through cable has been connected to pins 4 and 9 of the
COM port on the SVG display, and the other end has been connected to the COM
port on the ECC800-Pro.
Procedure
Step 1 Set SVG display parameters.
1.
Step 2 Add an SVG.
1.
2.
Issue 02 (2020-09-07)
NO TE
Pin 4 defines 485+, and pin 9 defines 485–.
Tap Expert Setting. On the displayed SVG communication settings screen, set
ID to 1 and Baud to 9600.
NO TE
ID is the communication address, ranging from 1 to 255. This operation uses 1 as an
example.
Figure 8-10 Setting SVG parameters
Log in to the ECC800-Pro WebUI as an administrator.
Add an SVG.
Table 8-7 Adding an SVG
Path
Parameter
Choose
Device
System
attribute
Settings >
Device Type
Device
Management
Copyright © Huawei Technologies Co., Ltd.
Setting
Select PDU from the drop-down list box.
Select SVG-In-Power from the drop-down
list box.
8 FAQ
270