ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Step 6 On the IP Device 1-5 tab page, set Enable online detection IP device 1 to
Enable.
Step 7 Click Submit.
Step 8 Specify IP device 1 address.
Step 9 Click Submit.
Step 10 (Optional) If you need to change the name of an IP device, perform the following
steps:
1.
2.
3.
----End

8.1.7.26 How Can I Set and Add an Independent Deployment AI_DI Unit?

Prerequisites
One end of the straight-through cable has been connected to the COM_IN port on
the independent deployment AI_DI unit, and the other end has been connected to
the COM port on the ECC800-Pro collector or ETH converter.
Procedure
Step 1 Set monitoring parameters for the independent deployment AI_DI unit.
Set the address of the independent deployment AI_DI unit to 1 or 2 by setting its
DIP switch.
The DIP switch consists of toggle switches 1–4 (from left to right). Toggle switches
1–3 specify the address of the independent deployment AI_DI unit. Toggle switch 4
specifies the address of the RS485 build-out resistor. 1 indicates ON, and 0
indicates OFF.
The device address for the independent deployment AI_DI unit can only be set to 1 or 2.
Table 8-22 Setting a device address
Address
1
Issue 02 (2020-09-07)
NO TE
● Set IP device 1 address to the IP address of IP device 1. For example, set IP device 1
address to 192.168.2.137.
● Add other IP devices in the same way.
Choose System Settings > Signal Name Modify. The Batch Signal
Configuration page is displayed.
Set Device type to ECC800, set Device name to ECC800, and click OK.
On the query result tab page, set the new signal name of IP device 1 to XXX
and click Submit.
NO TE
Toggle Switch 1
OFF
Copyright © Huawei Technologies Co., Ltd.
Toggle Switch 2
ON
8 FAQ
Toggle Switch 3
ON
294