ECC800 Data Center Controller
User Manual
3.
4.
Step 2 Add a PDC DC meter.
1.
2.
Table 5-14 Adding a PDC DC meter
Path
System
Settings >
Device
Management
3.
----End
5.3.17 Setting and Adding an Independent Deployment AI/DI
Unit
Context
In this example, the Independent Deployment AI/DI Unit is connected to the COM3 port on
the ECC800.
Issue 02 (2019-02-28)
Set the communications address. Tap the ID under Device ID on the displayed setting
screen, enter 1 (the actual value prevails) using the keyboard that pops up, and then tap
Enter.
Press the restart button at the rear of the monitoring screen. Then the parameters take
effect.
The communications address is 1 by default.
Log in to the ECC800 WebUI as an administrator.
Add a PDC DC meter.
Parameter
Name
Device type
Connect to
Communicatio
ns port
Device
address
Click Connect Test to check whether the PDC DC meter connects to the ECC800
properly.
If the PDC DC meter connects to the ECC800 properly, click Add Device.
If the PDC DC meter does not connect to the ECC800 properly, check whether the
cable between the PDC DC meter and the ECC800 is connected properly, whether
the PDC DC meter and ECC800 are running properly, and whether the input
parameters are consistent with the PDC DC meter parameters.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select DC Meter from the drop-down list box.
Select ECC800 from the drop-down list box.
Select COM2 from the drop-down list box.
NOTE
The setting example indicates that the DC meter is
connected to the COM2 port on the ECC800. If the DC
meter is connected to another port, enter the number of the
connected port.
In this example, Device address is set to 1. During
actual configuration, set the device address for the
PDC DC meter based on the actual situation.