Commissioning An Access Control Device And A Cabinet Electronic Lock - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Procedure
Step 1 Set parameters for a door status sensor.
1.
2.
3.
Step 2 Check the door status sensor functions.
Table 5-39 Commissioning the sensor
Check Method
Open the cabinet door.
----End
5.7.7 Commissioning an Access Control Device and a Cabinet
Electronic Lock
If an access control device and cabinet electric lock are installed, perform the following steps
to configure it.
Prerequisites
Context
Add or modify user on the Access User Management page, add or modify user rights on the
Access Right Management page. The added or modified user accounts and rights are saved
only in the ECC800 main control module. The modified rights take effect in the access control
device only after you click Synchronize Permission on the Access Right Management
page.
Issue 02 (2019-02-28)
In this example, the door status sensor is connected to the AI/DI_1 port on the rack environment unit 1.
Log in to the ECC800 WebUI as an administrator.
Choose Monitoring > IT Cabinet > IT Cabinet 1 > Cabinet Collector1 > Running
Parameters > AI/DI_1 Port Settings.
Set AI/DI_1 sensor to Enable, and click Submit.
When the fingerprint reader is connected to the ECC800 for the first time, the
permissions need to be synchronized.
If multiple access control devices and cabinet electronic locks are connected,
commission one access control device and cabinet electronic lock first, and then
commission the other access control devices and cabinet electronic locks in the same
way.
Copyright © Huawei Technologies Co., Ltd.
Normal Connection Status
If the Front door open or Rear door open alarm is
enabled, Front door open or Rear door open is
generated on the active alarm page of the app or
WebUI.