ECC800 Data Center Controller
User Manual
6.
Step 3 Set an alarm for card readers.
Set Logical level configuration for reader removed based on the fingerprint reader
configured for the access control system.
Table 5-40 Setting method
Cable Connection Scenario
The card reader with a keypad is
connected to WG_1 port on the access
actuator.
The card reader with a keypad is
connected to WG_2 port on the access
actuator.
Step 4 Check the functions of the access control device and access actuator.
Issue 02 (2019-02-28)
Figure 5-17 Synchronizing access permissions
When Synchronization Status is Synchronized for the related devices, close the
Synchronize Access Permission page.
If the access control system uses a Card and password reader, choose Monitoring >
Aisle > Access Actuator Group > Access Actuator n on the ECC800 WebUI, click
Running Parameters, and set Logical level configuration for reader removed of the
corresponding card reader to High level alarm.
If the access control system uses a Card, Card and fingerprint, or Card, password
and fingerprint reader, retain the default value Low level alarm for Logical level
configuration for reader removed.
Copyright © Huawei Technologies Co., Ltd.
Setting Method
Set Logical level configuration for reader 1
removed to High level alarm. Logical level
configuration for reader 2 removed remains as
Low level alarm.
Set Logical level configuration for reader 2
removed to High level alarm. Logical level
configuration for reader 1 removed remains as
Low level alarm.
5 Power-On Commissioning
140