5.3.3 Setting and Adding a UPS5000-E

Prerequisites
In this example, a straight-through cable is used to connect the UPS5000-E to the COM port
on the ETH converter.
When connecting devices, you are advised to add devices one by one and ensure that the view
is consistent with the real object. If all devices have been added and powered on, only the
BLINK function of the ETH converter can be used to identify the mapping between the
UPS5000-E and ETH converter.
Procedure
Step 1 Set the UPS5000-E monitoring parameters.
1.
2.
3.
Issue 02 (2019-02-28)
Parameter
Name
Device address
Click Connect Test to check whether the UPS2000-G connects to the ECC800 properly.
If the UPS2000-G connects to the ECC800 properly, click Add Device.
If the UPS2000-G does not connect to the ECC800 properly, check whether the
cable between the UPS2000-G and the ECC800 is connected properly, whether the
UPS2000-G and ECC800 are running properly, and whether the input parameters
are consistent with the UPS2000-G parameters.
The section describes how to add a UPS2000-G in a single UPS scenario. In a parallel UPS scenario, if
the common communications address of the Modbus card is added to the ECC800, all UPS2000-Gs can
be connected to the ECC800.
On the displayed screen after UPS5000-E startup, tap System Info.
Choose System Info > Settings, enter the user name admin and password 000001, and
press
.
Tap Communication and set RS485 baud rate to 9600, and RS485 address to 1 on the
displayed communication settings screen.
Copyright © Huawei Technologies Co., Ltd.
Setting
In this example, Device address is set to 1. During
actual configuration, set the device address for the
UPS2000-G based on the actual situation.
5 Power-On Commissioning