How To Associate An Alarm Severity With A Do Output; How Can I Handle Do Association Failure - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Step 6 (Optional) Select ECC800 from Linked Device if you select Device for the Linkage Type.
Step 7 Set DO1 or DO2 to Yes and click OK.
Select a DO not used by other functions. Otherwise, the association setting fails.
----End

9.1.15 How to Associate an Alarm Severity with a DO Output?

Context
Procedure
Step 1 Log in to the ECC800 WebUI as an administrator.
Step 2 Choose Monitoring > System > ECC800.
Step 3 On the Running Parameters tab page, click Alarm Level Link.
Step 4 Select DO1 or DO2 after Critical alarm association.
Step 5 Click Submit.
----End

9.1.16 How Can I Handle DO Association Failure?

Prerequisites
Context
Issue 02 (2019-02-28)
After an alarm severity and a DO output are associated, the device connected to the DO
port will act if an alarm of the corresponding severity is generated.
This section describes how to associate a critical alarm with a DO output.
The system type is FusionModule2000.
Critical alarm association, Major alarm association, Minor alarm association, and Warning alarm
association are all None by default.
You have obtained the IP address of the ECC800 as well as the user name and password
used for WebUI login.
A PC with an IP address in the same network segment as that of the ECC800 is prepared,
and the PC has connected to port WAN_1 on the ECC800.
If DO association fails, the DO port to be associated may be used by other functions.
Check whether the DO port is used.
Two ECC800 functions may use a DO port: PLC linkage and alarm linkage.
Copyright © Huawei Technologies Co., Ltd.
9 FAQ
206