Huawei ECC800 User Manual page 112

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Step 2 Add a PDU8000.
1.
2.
Table 5-7 Adding a PDU8000
Path
System
Settings >
Device
Management
3.
----End
Issue 02 (2019-02-28)
Figure 5-3 PDU8000 communication settings screen
Log in to the ECC800 WebUI as an administrator.
Add a PDU8000.
Parameter
Name
Device type
Connect to
Communications
port
Device address
Click Connect Test to check whether the PDU8000 connects to the ECC800 properly.
If the PDU8000 connects to the ECC800 properly, click Add Device.
If the PDU8000 does not connect to the ECC800 properly, check whether the cable
between the PDU8000 and the ECC800 is connected properly, whether the
PDU8000 and ECC800 are running properly, and whether the input parameters are
consistent with the PDU8000 parameters.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select PDU8000 from the drop-down list box.
Select ECC800 from the drop-down list box.
Select COM1 from the drop-down list box.
NOTE
The setting example indicates that the PDU8000 is
connected to the COM1 port on the ECC800. If the
PDU8000 is connected to another port, enter the number
of the connected port.
In this example, Device address is set to 1. During
actual configuration, set the device address for the
PDU8000 based on the actual situation.
5 Power-On Commissioning
103

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents