ECC800 Data Center Controller
User Manual
Procedure
Step 1 Set the T/H sensor device address.
1.
2.
Step 2 Add a T/H sensor.
1.
2.
Table 5-33 Adding a T/H sensor
Path
System
Settings >
Device
Management
3.
Step 3 Check functions of the T/H sensor.
Table 5-34 Function commissioning
Check Method
Check the running information
about the T/H sensor on the
WebUI.
Issue 02 (2019-02-28)
Go to the LCD screen of the T/H sensor. Press SET to go to the ADD screen.
Set the device address to 1 by pressing + or –.
Log in to the ECC800 WebUI as an administrator.
Add a T/H sensor.
Parameter
Name
Device type
Connect to
Communicatio
ns port
Device
address
Click Connect Test to check whether the T/H sensor connects to the ECC800 properly.
If the T/H sensor connects to the ECC800 properly, click Add Device.
If the T/H sensor does not connect to the ECC800 properly, check whether the cable
between the T/H sensor and the ECC800 is connected properly, whether the T/H
sensor and ECC800 are running properly, and whether the input parameters are
consistent with the T/H sensor parameters.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select T/H Sensor from the drop-down list box.
Select ECC800 from the drop-down list box.
Select COM3 from the drop-down list box.
NOTE
The setting example indicates that the T/H sensor is
connected to the COM3 port on the ECC800. If the T/H
sensor is connected to another port, enter the number of the
connected port.
In this example, Device address is set to 1. During
actual configuration, set the device address for the
T/H sensor based on the actual situation.
Normal Connection Status
Choose Monitoring > Aisle > T/H Sensor Group >
T/H Sensor n > Running Info, and check the current
T/H information of the cabinet.
5 Power-On Commissioning