Setting And Adding A Pdc Dc Meter - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Step 2 Add a PMAC615.
1.
2.
Table 5-13 Adding a PMAC615
Path
System
Settings >
Device
Management
3.
----End

5.3.16 Setting and Adding a PDC DC Meter

Prerequisites
Procedure
Step 1 Set the communications address for the PDC DC meter.
1.
2.
Issue 02 (2019-02-28)
Log in to the ECC800 WebUI as an administrator.
Add a PMAC615.
Parameter
Name
Device type
Connect to
Communications
port
Device address
Click Connect Test to check whether the PMAC615 connects to the ECC800 properly.
If the PMAC615 connects to the ECC800 properly, click Add Device.
If the PMAC615 does not connect to the ECC800 properly, check whether the cable
between the PMAC615 and the ECC800 is connected properly, whether the
PMAC615 and ECC800 are running properly, and whether the input parameters are
consistent with the PMAC615 parameters.
The model of the PDC is PDU8000-0630DCV5-HVA002 and the BOM number is
02403121.
In this example, a straight-through cable is used to connect the PDC DC meter to the
COM2 port on the ECC800.
Tap Settings on the screen after the PDC DC meter is started.
Enter 1 in the displayed password dialog box, tap Enter, and then tap Confirm to enter
the setting screen.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select PMAC615 from the drop-down list box.
Select ECC800 from the drop-down list box.
Select COM3 from the drop-down list box.
NOTE
The setting example indicates that the PMAC615 is
connected to the COM3 port on the ECC800. If the
PMAC615 is connected to another port, enter the number
of the connected port.
In this example, Device address is set to 8. During
actual configuration, set the device address for the
PMAC615 based on the actual situation.
5 Power-On Commissioning
111