Step 3 Set the running parameters and control parameters for the NetCol5000-C030 on the WebUI.
1.
2.
3.
4.
----End
5.3.7 Setting the NetCol5000-A025 or NetCol5000-A010
Parameters(over MAC-Modbus)
Prerequisites
In this example, a straight-through cable is used to connect the NetCol5000-A025 or
NetCol5000-A010 to the PoE port on the smart ETH gateway.
Context
Procedure
Step 1 Set the running parameters and control parameters for the 25 kW smart cooling product on the
ECC800 WebUI.
1.
2.
3.
4.
Issue 02 (2019-02-28)
whether the NetCol5000-C030 and ECC800 are running properly, and whether the
input parameters are consistent with the NetCol5000-C030 parameters.
Log in to the ECC800 WebUI as an administrator.
Choose Monitoring > Air Conditioner > NetCol5000-C0301.
0301 in NetCol5000-C0301 is variable and subject to change with the smart cooling product model and
connection sequence. 030 indicates the 30 kW model, and 1 indicates the smart cooling product
connection sequence. The displayed value prevails.
On the Running Parameters tab page, set smart cooling product running parameters,
temperature and humidity parameters, and alarm parameters.
On the Controls tab page, set the smart cooling product control parameters (such as
on/off control parameters).
The following describes how to set the NetCol5000-A025 parameters. The way of
setting the NetCol5000-A010 parameter is similar.
The NetCol5000-A025 communicates with the ECC800 over MAC-Modbus. After
connecting to the ECC800 successfully, the NetCol5000-A025 can be identified
automatically without setting communications parameters.
After the smart cooling product is replaced, set smart cooling product parameters on the
ECC800 WebUI.
Log in to the ECC800 WebUI as an administrator.
Choose Monitoring > Air Conditioner > NetCol5000-A0251.
0251 in NetCol5000-A0251 is variable and subject to change with the smart cooling product model and
connection sequence. 025 indicates the 25 kW model, and 1 indicates the smart cooling product
connection sequence. The displayed value prevails.
On the Running Parameters tab page, set running parameters, temperature and
humidity parameters, and alarm parameters.
On the Controls tab page, set the smart cooling product control parameters (such as
on/off control parameters).