8.7.20 How Can I Set and Add a NetCol5000-C(030, 032)/
NetCol5000-C(065, 080) Parameters (over Modbus TCP)?
Prerequisites
One end of the straight-through cable has been connected to the FE port on the
NetCol5000-C(030, 032) or the NetCol5000-C(065, 080) main control board, and
the other end has been connected to the POE port on the ETH converter.
Context
The following describes how to set and add a NetCol5000-C(030, 032).
Procedure
Step 1 Set NetCol5000-C(030, 032) monitoring parameters.
1.
2.
3.
Issue 04 (2021-10-09)
NO TE
After the NetCol5000-A025 parameters are set, the ECC800-Pro can automatically identify
the automatic access of the NetCol5000-A025.
Log in to the ECC800-Pro WebUI as an administrator.
Choose Monitoring > Cooling > NetCol5000-A0251.
NO TE
– 1 in NetCol5000-A0251 is variable and subject to change with the smart cooling
product model and connection sequence. The displayed value prevails.
On the Running Parameters tab page, set running parameters.
On the Controls tab page, set the smart cooling product control parameters
(such as on/off control parameters).
CA UTION
After the smart cooling product is shut down, the temperature of the smart
module increases and data running is affected. Exercise caution when
performing this operation.
Enter the NetCol5000-C(030, 032) home page, click Settings, choose user
name admin and enter password 000001. After login, the settings screen of
the NetCol5000-C(030, 032) is displayed.
Choose Settings > Comm Settings > LAN IP Settings, set LAN IP assigning
mode to Automatic(DHCP), and tap Submit.
Choose Settings > Comm Settings > Modbus Settings, and set Connection
mode to Server and client, Server encryption to Enable.