ECC800 Data Center Controller
User Manual
Procedure
Step 1 Set the UPS5000 monitoring parameters.
1.
2.
3.
Step 2 Add a UPS5000.
1.
2.
3.
4.
----End
Issue 04 (2021-10-09)
On the displayed screen after UPS5000 startup, tap System Info.
Choose System Info > Settings, enter the user name admin and password
000001, and tap
Tap Comm. Settings > RS485 Settings. On the RS485 communication
settings screen, set Address based on the actual plan and set Baud rate to
9600.
Log in to the ECC800-Pro WebUI as an administrator.
Add a UPS5000.
Table 8-5 Adding a UPS5000
Path
Parameter
Choose
Device
System
attribute
Settings >
Device Type
Device
Management
and click Add
Connect To
Device. The
parameters
for adding
Communicati
devices are
ons Port
displayed.
Device
Address
Click Test Connect to check whether the UPS5000 is properly connected to
the ECC800-Pro.
If the connection succeeds, click Confirm. The connected devices are
displayed in the Number of connected devices list.
If the connection fails, check whether the device is properly connected to
the ECC800-Pro, whether the device and ECC800-Pro are running
properly, and whether the parameter settings are consistent with the
device parameters.
Choose Monitoring > System > ETH Converter Group > ETH Converter n >
Running Parameters and set Device name to ETH Converter n_Device
name.
Copyright © Huawei Technologies Co., Ltd.
.
Setting
Select UPS from the drop-down list box.
Select UPS5000 from the drop-down list
box.
Select ETH Converter n from the drop-
down list box.
Select COM1/COM2 from the drop-down
list box.
Enter the actual communication address of
the UPS5000.
8 FAQ
307