ECC800 Data Center Controller
User Manual
4.
Step 4 If there are multiple eLights, repeat
----End
5.8 Commissioning the PDU2000 (for
FusionModule500/800)
When the system type is FusionModule500/800 and a PDU2000 is installed,
perform the following steps to configure it.
Issue 04 (2021-10-09)
Table 5-13 Function commissioning
Item
Associated
alarm severity
NOTE
After you set the alarm severity, the eLight indicator is off if no alarm is generated.
(Optional) When the eLight is connected to a cabinet, commission the cabinet
light.
–
When you open the front door of the cabinet, the tube light connected at
the front door turns white.
–
When you open the rear door of the cabinet, the tube light connected at
the rear door turns white.
–
When the front or rear door of the cabinet is closed, the corresponding
light color is displayed based on the setting of Associated alarm
severity.
Copyright © Huawei Technologies Co., Ltd.
Alarm Severity
Selection
Critical
Critical, Major
Critical, Major,
Minor
Critical, Major,
Minor, Warning
None
Step 1–Step
5 Power-On Commissioning
Description
If there is a critical alarm, the
eLight strip light turns on with a
red light.
If there are multiple alarms, the
eLight strip light preferentially
turns on with a light
corresponding to the high-
severity alarm. After the high-
severity alarm is cleared, the
eLight strip light turns on with a
light corresponding to the low-
severity alarm.
NOTE
– Critical: red light
– Major: orange light
– Minor: yellow light
– Warning: gray light
The eLight strip light is steady
blue (atmosphere light).
3.