How To Set And Add A Netcol5000-C(030, 032)/Netcol5000-C(065, 080) Parameters (Over Modbus Tcp) - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
----End
8.1.6.15 How to Set and Add a NetCol5000-C(030, 032)/NetCol5000-C(065,
080) Parameters (over Modbus TCP)?
Prerequisites
One end of the straight-through cable has been connected to the FE port on the
NetCol5000-C(030, 032) or the NetCol5000-C(065, 080) main control board, and the other
end has been connected to the POE port on the ETH converter.
Context
The following describes how to set and add a NetCol5000-C(030, 032).
Procedure
Step 1 Set NetCol5000-C(030, 032) monitoring parameters.
1.
2.
3.
Step 2 Set the running parameters and control parameters for the NetCol5000-C(030, 032) on the
WebUI.
1.
2.
3.
4.
After the smart cooling product is shut down, the temperature of the smart module increases
and data running is affected. Exercise caution when performing this operation.
----End
Issue 06 (2020-04-22)
Enter the NetCol5000-C(030, 032) home page, click Settings, choose user name admin
and enter password 000001. After login, the settings screen of the NetCol5000-C(030,
032) is displayed.
Choose Settings > Comm Settings > IP Settings, set IP assigning mode to
Automatic(DHCP), and tap Submit.
Choose Settings > Comm Settings > Modbus Settings, and set Connection mode to
Server and client, Server encryption to Enable.
After setting parameters for the NetCol5000-C(030, 032), the ECC800-Pro discovers the access
from the smart cooling product automatically.
The earlier version has Protocol setting on the screen. The actual screen prevails.
Log in to the ECC800-Pro WebUI as an administrator.
Choose Monitoring > Cooling > NetCol5000-C0301.
1 in NetCol5000-C0301 is variable and subject to change with the smart cooling product model and
connection sequence. The displayed value prevails.
On the Running Parameters tab page, set smart cooling product running parameters.
On the Controls tab page, set the smart cooling product control parameters (such as
on/off control parameters).