Step 3 Set the running parameters and control parameters for the NetCol5000-C030 on the WebUI.
1.
2.
3.
4.
After the smart cooling product is shut down, the temperature of the smart module increases
and data running is affected. Exercise caution when performing this operation.
----End

8.1.6.17 How to Set and Add an IP Device?

Prerequisites
Context
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Choose Monitoring > System > ECC800 > Running Parameters.
Step 3 Click Unhide All Advanced Signals, on the IP Device Detection Parameters tab page, set
Online detection timeout interval to 29. The value range is 10 to 60 seconds. Click Submit.
Issue 06 (2020-04-22)
If the NetCol5000-C030 does not connect to the ECC800-Pro properly, check
whether the cable between the NetCol5000-C030 and the ECC800-Pro is connected
properly, whether the NetCol5000-C030 and ECC800-Pro are running properly, and
whether the input parameters are consistent with the NetCol5000-C030 parameters.
Log in to the ECC800-Pro WebUI as an administrator.
Choose Monitoring > Cooling > NetCol5000-C0301.
1 in NetCol5000-C0301 is variable and subject to change with the smart cooling product model and
connection sequence. The displayed value prevails.
On the Running Parameters tab page, set smart cooling product running parameters.
On the Controls tab page, set the smart cooling product control parameters (such as
on/off control parameters).
An IP device is connected to the ECC800-Pro over a switch. The device and
ECC800-Pro have been powered on.
You have obtained the IP address of the IP device.
IP devices, such as ATMs, are devices with IP attributes in equipment room or site. By
adding an IP device, you connect the device to the ECC800-Pro in the same network so
that the ECC800-Pro monitors the device status. If the IP device is offline, the
ECC800-Pro will report a disconnection alarm on its WebUI.
In the LAN scenario, the IP devices and the ECC800-Pro must be in the same network.
Following is a procedure example about how to add five IP devices with the online
detection timeout interval being 29 seconds.