8.1.38 How Should I Link the AI/DI Alarm with the Alarm Beacon
over the ECC800-Pro WebUI
Prerequisites
The alarm beacon is connected to the DO port on the ECC800-Pro.
Context
After the AI/DI alarm is linked with the alarm beacon, if smoke is detected inside the smart
module, the alarm beacon connecting to the corresponding DO port will generate an audible
and visual alarm.
This section describes how to set an alarm linkage by linking output dry contact of the smoke
DI alarm on the AI/DI_1 sensor to the DO port.
Procedure
Step 1 Choose System Settings > Alarm Parameter > Alarm Linkage.
Step 2 Select ECC800 for Device type, select Device Type or Device for Linkage type, and click
Confirm.
Step 3 Click Select in the Output Dry Contact list for AI/DI_1 DI alarm. On the Set Dry Contact
Outputs(ECC800) page, set DO to Yes and click OK.
Step 4 Click Select in the loudspeaker list for AI/DI_1 DI alarm. On the Please set the
sound(ECC800) page, set loudspeaker to Yes and click OK.
----End
8.1.39 How Should I Modify Device Names over the ECC800-Pro
WebUI?
Context
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Modify the device name.
Issue 06 (2020-04-22)
Select ECC800 from the Device name list if you have selected Device for Linkage type, and click
Confirm.
When a device name does not correspond to the actual location or needs optimizing, you
can modify the device name over the ECC800-Pro WebUI.
The following describes how to modify the name of the smart ETH gateway.