7.1 Routine Maintenance

Table 7-1 Routine maintenance for the PSU in the ECC800-Pro
Check Item
AC input
Output
voltage
Indicator
Fan
Operating
environment
Cable
connection
Table 7-2 Routine maintenance for the main control module in the ECC800-Pro
Check Item
Indicator
Network port
Issue 06 (2020-04-22)
Expected Result
Input voltage: 200–240 V AC
Frequency: 45–66 Hz
Output voltage: 53.5 V DC
(tolerance ± 5%)
The green indicator is steady
on, and the red indicator is
faulty.
No abnormal noise is
generated.
Ambient temperature:
–20° C to +50° C
Humidity: 0-95% RH
(non-condensing)
The cable connection is
secure.
Cables are not damaged.
Expected Result
The green indicator is steady
on or blinking.
The green indicator is steady
Copyright © Huawei Technologies Co., Ltd.
7

Maintenance

Troubleshooting
If the input voltage is abnormal, check
the power grid and input cable
connection.
If the output voltage is abnormal, check
the load power and cable connection.
Check the output voltage and determine
whether the PSU is faulty. If the PSU is
faulty, replace it.
If abnormal noise is generated, clean the
fan.
If the temperature or humidity is
abnormal, check the smart cooling
product status.
Secure loose cables.
Replace damaged cables.
Troubleshooting
If the indicator is off or any abnormal
condition occurs, see common faults and
troubleshooting to rectify the fault.
If the indicator status is abnormal, check