How Should I Set And Add A 5G Dc Power Supply (Mts9604B-N20B1) - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Path
Settings >
Device
Management
and click Add
Device. The
parameters for
adding devices
are displayed.
3.
----End
8.1.6.7 How Should I Set and Add a 5G DC Power Supply
(MTS9604B-N20B1)?
Prerequisites
One end of the straight-through cable has been connected to the COM1 port on the SMU11D
in the MTS9604B-N20B1 cabinet, and the other end has been connected to the COM port on
the ECC800-Pro collector or ETH converter.
Procedure
Step 1 Configure the northbound RS485 communication address.
Issue 06 (2020-04-22)
Parameter
Name
Device Type
Connect To
Communications
Port
Device Address
Click Test Connect to check whether the PDU8000 connects to the ECC800-Pro
properly.
If the PDU8000 connects to the ECC800-Pro properly, click Confirm. The
connected devices are displayed in the Number of connected devices list.
If the PDU8000 does not connect to the ECC800-Pro properly, check whether the
cable between the PDU8000 and the ECC800-Pro is connected properly, whether
the PDU8000 and ECC800-Pro are running properly, and whether the input
parameters are consistent with the PDU8000 parameters.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select PDU8000 from the drop-down list box.
Select ECC800 from the drop-down list box.
Select COM1 from the drop-down list box.
NOTE
The setting example indicates that the PDU8000 is
connected to the COM1 port on the ECC800-Pro. If the
PDU8000 is connected to another port, enter the number
of the connected port.
In this example, Device Address is set to 1. During
actual configuration, set the device address for the
PDU8000 based on the actual situation.