7.8.2 Configuring PUE User-defined Mode

Context
This section describes how to configure PUE for the integrated PDC connected.
The functions of configuration buttons for the PUE user-defined mode are described as
follows.
Table 7-5 PUE configuration buttons
No.
1
2
Procedure
Step 1 Log in to the ECC800 WebUI as an administrator.
Step 2 Choose System Settings > PUE Configuration.
Step 3 Ensure that PUE function is set to Enable.
Step 4 Set PUE configuration mode to User-defined, and click Submit.
Issue 02 (2019-02-28)
Figure 7-7 Querying the total electrical energy of system IT load output
Calculate the PUE of the smart module. PUE = Increment in total system input electrical
energy/Increment in total electrical energy of system IT load output = 10.0 kWh/6.0
kWh = 1.67