9.1.11 How to Associate an Alarm with a DO Output?

Context
Procedure
Step 1 Log in to the ECC800 WebUI as an administrator.
Step 2 Choose System Settings > Alarm Linkage.
Step 3 Set Select a device type to ECC800 and click Confirm.
Step 4 Select the alarm to be bound to a DO port, and click Select in the Output Dry Contact
column.
Step 5 Choose Device type or Device from Linkage Type.
Step 6 (Optional) Select ECC800 from Linked Device if you select Device for the Linkage Type.
Step 7 Set DO1 or DO2 to Yes and click OK.
Select a DO not used by other functions. Otherwise, the association setting fails.
----End
Exception Handling
If setting the association with the DO fails, perform troubleshooting by following instructions
in

9.1.12 How to Associate an Alarm Severity with a DO Output?

Context
Procedure
Step 1 Log in to the ECC800 WebUI as an administrator.
Step 2 Choose Monitoring > System > ECC800.
Step 3 On the Running Parameters tab page, click Alarm Level Link.
Step 4 Select DO1 or DO2 after Critical alarm association.
Issue 06 (2020-01-02)
After an alarm and a DO output are associated, the device connected to the DO port will
act if the alarm is generated.
This section describes how to associate an ECC800 alarm with a DO output.
9.1.13 How to Handle DO Association
After an alarm severity and a DO output are associated, the device connected to the DO
port will act if an alarm of the corresponding severity is generated.
This section describes how to associate a critical alarm with a DO output.
The system type is FusionModule2000.
Copyright © Huawei Technologies Co., Ltd.
Failure?.