ECC800 Data Center Controller
User Manual
6.
7.
8.
9.
Step 2 (Optional) Set functions on the infrared remote control module.
1.
2.
3.
4.
5.
----End

7.7 iCooling Function

Working Principles
iCooling is aimed at accelerating respond speed of the smart cooling product and to avoid
partial hot spots by distributing cold air based on requirements.
Issue 06 (2020-01-02)
Direct the smart cooling product remote control to the infrared receiving place on the
infrared remote control module, then press on the button once.
If you do not press on the button within 20s, the smart cooling product remote control will exit the
learning mode due to a timeout. You can click Learning the startup instruction on the ECC800 WebUI
and start the learning mode again.
On the Controls tab page, choose Exiting the learning mode, and click Submit.
On the Controls tab page, choose Air conditioner startup, and click Submit. On the
displayed Re-Authentication window, enter password in the Login Password box, and
click Submit.
Check whether the smart cooling product starts. If it starts, the control function works; if
it cannot start, rectify the fault and perform the preceding steps again.
After you perform Learning the startup instruction on the WebUI, check the indicator status. If
the indicator on the infrared remote control module blinks yellow, it indicates that the infrared
remote control module enters the infrared learning state. If the green indicator blinks, it indicates
learning success of the key code. If the indicator is steady yellow, it indicates learning failure and
you need to rectify the faults and perform Learning the startup instruction again.
After you perform smart cooling product startup, check whether the smart cooling product starts.
If it starts, the control function works; if it cannot start, rectify the fault and perform the preceding
steps again.
After the device power-on, if the yellow indicator is steady on, it indicates that the
device has never learnt the infrared coding successfully. If the green indicator blinks, it
indicates that the device has learnt the infrared coding successfully. And the infrared
remote control module enters normal operating mode by default.
Press the SW button on the infrared remote control module for more than 3s. Then the
indicator blinks yellow and the infrared remote control module enters learning operating
mode.
Press the SW button once quickly and the infrared remote control module enters the
waiting state for learning. Direct the smart cooling product remote control to the infrared
receiving place on the infrared remote control module, and press the power button once.
If the green indicator blinks, it indicates learning success of the first key code.
The device will quit learning operating mode automatically once finish learning.
After the smart cooling product is shut down, direct the infrared remote control module
to the smart cooling product and press the SW button once.
Check whether the smart cooling product starts. If it starts, the control function works; if
it cannot start, rectify the fault and perform the preceding steps again.