5.3.20 Setting and Adding an AC or DC Meter

Context
This section describes how to set and add an AC meter, and provides a reference for how to
set and add a DC meter.
Procedure
Step 1 Set monitoring parameters for the AC meter.
1.
2.
3.
Step 2 Add the AC meter.
1.
2.
Table 5-17 Setting parameters for the AC meter
Path
Home >
Device
Issue 06 (2020-01-02)
Parameter
Name
port
Device address
Click Connect Test to check whether the 48 V DC power supply device connects to the
ECC800 properly.
If the device connects to the ECC800 properly, click Add Device.
If the device does not connect to the ECC800 properly, check whether the cable
between the device and the ECC800 is connected properly, whether the device and
ECC800 are running properly, and whether the input parameters are the consistent
with the device parameters.
On the AC meter screen displayed after the startup, press E to go to the login screen.
Type the password 1000, and press H to go to the Settings screen.
Press H to go to the Address Settings screen. Then, set Communication Address to 1
(value range: 1-247) by pressing the up and down keys, and press H.
Log in to the ECC800 WebUI as an administrator.
Add the AC meter.
The setting example indicates that the AC meter is connected to the COM2 port on the
ECC800. If the AC meter is connected to another port, set the number of the connected
port.
Parameter
Name
Device type
Connect to
Copyright © Huawei Technologies Co., Ltd.
Setting
In this example, set Device address to 1. Set the
actual device address of the 48 V DC power supply
device during operations.
Setting
Select AC Meter from the drop-down list box.
Select ECC800 from the drop-down list box.