ECC800 Data Center Controller
User Manual
Table 3-6 PSU indicator description
Indicator
Issue 06 (2020-01-02)
Color
Name
Green
Power indicator
Yellow
Alarm indicator
Red
Fault indicator
Copyright © Huawei Technologies Co., Ltd.
Status
Description
Steady on
The converter has a power
input.
Off
The converter has no power
input or is faulty.
Blinking at
The converter is being
long
queried (the indicator blinks
intervals
at 0.5 Hz, on for 1s and then
off for 1s).
Blinking at
The converter application
short
program is being loaded (the
intervals
indicator blinks at 4 Hz, on
for 0.125s and then off for
0.125s).
Steady on
The converter generates a
forewarning indicating that
power will be limited due to
ambient overtemperature, or
generates a protection
shutdown alarm due to
ambient overtemperature or
undertemperature.
Power input overvoltage or
undervoltage protection
Reverse DC input connection
Slight current imbalance
Output overvoltage
Hibernation
Off
The converter generates no
protection alarms.
Blinking at
The communication between
long
the converter and the outside
intervals
is interrupted (the indicator
blinks at 0.5 Hz, on for 1s
and then off for 1s).
Steady on
The converter locks out due
to output overvoltage.
The converter delivers no
output due to internal faults.
Off
The converter is working
properly.