Third-Party Nms Management (Over Snmp); Connecting The Communications Cable; Setting Snmp Management Parameters - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual

6.2 Third-party NMS Management (over SNMP)

6.2.1 Connecting the Communications Cable

6.2.2 Setting SNMP Management Parameters

Prerequisites
Before setting SNMP parameters, obtain the information listed as follows from the NMS.
Table 6-3 Information obtained from the NMS
Item
SNMP version
SNMP port number
Read community
name
Write community
name
User name
MD5/SHA password
DES/AES password
Trap target address
Trap port
Issue 06 (2020-01-02)
Figure 6-1 Adding an ECC800 device to the modular
Click OK, and you can view the task information, including Type, Device Name, Region, Progress,
Status, Start Time, End Time, and Information in the displayed Progress window.
During binding of the ECC800 for the first time, the screen will be locked indefinitely when the
progress bar reaches 30%, and displays Loading device profile. Please try it later. The actual
operation results prevail.
Default
Value
SNMPv3
161
N/A
N/A
N/A
N/A
N/A
N/A
162
Copyright © Huawei Technologies Co., Ltd.
Description
SNMP version and port number used by the ECC800
and NMS. The SNMP versions include SNMPv1,
SNMPv2c, and SNMPv3.
If you use SNMPv1 or SNMPv2c, enter the read and
write community names that comply with the NMS.
Otherwise, the ECC800 will not connect to the
NMS. The read community name must be different
from the write community name.
To enhance the security, you need a user name and
password for authentication if you use SNMPv3.
After the authentication succeeds, the ECC800 can
communicate with the NMS.
IP address of the NMS server.
Port defined by the user.
6 Remote Management