ECC800 Data Center Controller
User Manual
Check Method
----End
5.9.7 Commissioning an Access Control Device and a Cabinet
Electronic Lock
If an access control device and cabinet electric lock are installed, perform the following steps
to configure it.
Prerequisites
A maximum of two access actuators are supported.
When the fingerprint reader is connected to the ECC800 for the first time, the permissions
need to be synchronized.
Context
Add or modify user on the Access User Management page, add or modify user rights on the
Access Right Management page. The added or modified user accounts and rights are saved
only in the ECC800 main control module. The modified rights take effect in the access control
device only after you click Synchronize Permission on the Access Right Management
page.
Procedure
Step 1 Set access user management.
1.
2.
Issue 06 (2020-01-02)
Choose System Settings > Access User Management to enter the access user
information page. The system supports the management of various access permissions
through the access card, password, and fingerprint.
Click Add to enter the page for adding users. On the Basic Info tab page, enter User
name.
Password: Enter the password for the new user.
Card number: The card number can be recorded directly or by swiping the card.
Record directly: Type the access card number in the text box.
Record by swiping the card: Click Swipe Card and place the card on the
access control device. The card number is automatically recorded.
Fingerprint: On the Fingerprint tab, select Finger Print for Fingerprint reader
and click Collect. On the Please collect fingerprint page, click OK. Then put your
finger on the fingerprint reader to collect the fingerprint after hearing the voice
Copyright © Huawei Technologies Co., Ltd.
Normal Connection Status
is generated on the active alarm page of the app or
WebUI.
5 Power-On Commissioning