ECC800 Data Center Controller
User Manual

5.1 Setting the Date and Time

Procedure
Step 1 Choose System Settings > Time Settings.
Step 2 Set the time zone, date, and time, and click Submit.
Step 3 (Optional) If the NTP server is used for time synchronization, select NTP Server Sync, set
NTP Primary Server IP, NTP Backup Server IP, Port Number, and Sync Interval (Min),
and click Submit.
----End
5.2 Checking System Type and Setting Micro-module
Name
Context
Procedure
Step 1 Choose System Settings > Micro-Module Settings, and check whether System Type is
consistent with the type of the current micro-module.
If the system type is not consistent with the type of the current micro-module, please choose
the follows operates, in this example, the system type is changed to FusionModule1000A.
Issue 06 (2020-01-02)
5
Site ID: Site network fault alarms are sent to the specified mobile phone numbers of
maintenance engineers by SMS. After the system site ID is changed, the new site ID will
be displayed in the short message content (for example, XXX device communication
interruption) so that maintenance engineers will know the site where the fault has
occurred.
System type: FusionModule500, FusionModule800, FusionModule2000,
FusionModule1000B, and FusionModule1000A can be selected based on the actual
project type configuration.