Setting And Adding A Pmac615 Ac Meter - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual

5.3.13 Setting and Adding a PMAC615 AC Meter

Prerequisites
The model of the single-phase AC meter for the lighting control box is PMAC615.
In this example, a straight-through cable is used to connect the PMAC615 to the COM3 port
on ECC800.
Procedure
Step 1 Set the PMAC615 communications address.
1.
2.
Step 2 Add a PMAC615.
1.
2.
Table 5-10 Adding a PMAC615
Path
Home > Device
Management
Issue 06 (2020-01-02)
After the PMAC615 is started, press
screen is displayed. Press
communications address setting screen.
Press
and a blinking cursor is displayed. Press
communications address (ranging from 1 to 247). Then press
address setting.
Figure 5-9 PMAC615 communications address
Ensure that the baud rate of the PMAC615 (the default baud rate is 9600) is consistent with that of the
COM3 port on the ECC800.
Log in to the ECC800 WebUI as an administrator.
Follow the instructions in the following table to add the PMAC615.
Item
Device type
Connect to
Communications
port
Device address
Copyright © Huawei Technologies Co., Ltd.
on the displayed screen and the configuration
until the ID prompt is displayed, indicating the
Setting
Select PMAC615 from the drop-down list box.
Select ECC800 from the drop-down list box.
Select COM3 from the drop-down list box.
In this example, Device address is set to 8. During
actual configurations, set the device address for the
PMAC615 based on the actual situation.
5 Power-On Commissioning
to modify the
to confirm the
106